MODEL | 12V 400W | 15V 400W | 24V 400W | 36V 400W | 48V 400W | |
OUTPUT | DC VOLTAGE | 12V | 15V | 24V | 36V | 48V |
RATED CURRENT | 33.3A | 26.6A | 16.6A | 11A | 8.33A | |
CURRENT RANGE | 0~33.3A | 0~26.6A | 0~16.6A | 0~11A | 0~8.33A | |
RATED POWER | 400W | 400W | 400W | 400W | 400W | |
RIPPLE& NOISE (MAX.) | 150mVp-p | 150mVp-p | 150mVp-p | 150mVp-p | 200mV | |
VOLTAGE TOLERANCE | ±1% | ±1% | ±1% | ±1% | ±1% | |
SETUP , RISE TIME | 1000ms, 50ms/230VAC 1000ms,50ms/115VAC at full load | |||||
HOLD UP TIME(Typ.) | 20ms/230VAC 16ms/115VAC at full load | |||||
INPUT | VOLTAGE RANGE | 85~132VAC/170~264VAC | ||||
FREQUENCY RANGE | 47~63Hz | |||||
POWER FACTOR(Typ.) | PF>0.6/220VAC | |||||
EFFICIENCY(Typ.) | 75% | 78% | 80% | 83% | 84% | |
AC CURRENT(Typ.) | 7A/115VAC 4A/230VAC | |||||
INRUSH CURRENT(Typ.) | 40A/115VAC 60A/230VAC | |||||
SHORT CIRCUIT | protection type: recovers automatically after fault condition is removed | |||||
PROTECTION | OVER LOAD | 105~135% hiccup mode , auto-recovery | ||||
DC ADJ. RANGE | 115%~135% Cut off the output , auto-recovery | |||||
ENVIRONMENT | WORKING TEMP | -20℃~ +60℃ | ||||
WORKING HUMIDITY | 20%~90%RH | |||||
STORAGE TEMP , HUMIDITY | -40℃~+85℃,10%~90%RH | |||||
SAFETY&EMC | SAFETY STANDARDS | CE,ROHS | ||||
WITHSTAND VOLTAGE | I/P-O/P:1.5KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC | |||||
EMC TESTING STANDARD | EN55015:2006;EN61547:1995+A1:2000;EN61000-3-2:2006; | |||||
EN61000-3-3:1995+A2:2005;EN61347-1:2001;EN61347-2-13:2006 |